*3: Logging function should be used with API instructions.
*4: Disconnecton detecton can only be used in the modes of 4 mA to 20 mA and 1V to 5 V.
Functional specifications for the analog-to-digital conversion Voltage Input
Analog-to-Digital
Conversion
Voltage Input
Rated Input Range
-10V~10V
0V~10V
±5V
0V~5V
1V~5V
Rated Conversion
Range
K-32000
~
K32000
K0~K32000
K-32000
~
K32000
K0~K32000 K0~K32000
Hardware Input Limit*
1
-
10.12V~10.12V
-0.12V~10.12V
-5.06V~5.06V -0.06V~5.06V 0.95V~5.05V
Conversion Limit*
2
K-32384
~
K32384
K-384~K32384
K-32384
~
K32384
K-384~K32384
K-384~K32384
*1: If the input signal exceeds the hardware input limit, the module only shows the maximum value. If the input
signal is below the lower limit, it only shows the minimum value. And an error flag will be set.
*2: If the input signal exceeds the hardware input limit, it also exceeds the conversion limit and a conversion
limit error appears. For example in the voltage input mode (-10 V to +10 V), when the input signal is 10.15 V,
exceeding the hardware upper limit, it also exceeds the conversion upper limit. The module uses the upper
limit value (32384) as the input signal and a conversion limit error appears.
Functional specifications for the analog-to-digital conversion Current Input
Analog-to-Digital
Conversion
Current Input
Rated Input Range
±20mA
0mA~20mA
4mA~20mA
Rated Conversion
Range
K-32000
~
K32000
K0~K32000 K0~K32000
Hardware Input Limit*
1
-20.24mA~20.24mA
-0.24mA~20.24mA
3.81mA~20.19mA
Conversion Limit*
2
K-32384~ K32384
K-384~K32384
K-384~K32384
*1: If the input signal exceeds the hardware input limit, the module only shows the maximum value. If the input
signal is below the lower limit, it only shows the minimum value. And an error flag will be set.
*2: If the input signal exceeds the hardware input limit, it also exceeds the conversion limit and a conversion
limit error appears. For example in the voltage input mode (4 mA to 20 mA), when the input signal is 0 mA,
exceeding the hardware upper limit, it also exceeds the conversion upper limit. The module uses the upper
limit value (-384) as the input signal and a conversion limit error appears.
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta AS332P-A and is the answer not in the manual?

Delta AS332P-A Specifications

General IconGeneral
BrandDelta
ModelAS332P-A
CategoryControl Unit
LanguageEnglish

Related product manuals