9.2 Error Message & Trouble Shooting
Table 9-2 Error Message
ERROR
Message
Possible cause
Action
AC Freq
High
1. Actual utility frequency is over
the OFR setting
2. Incorrect country setting
3. Detection circuit malfunction
1. Check the utility frequency on the inverter
terminal
2. Check country setting
3. Check the detection circuit inside the inverter
AC Freq
Low
1. Actual utility frequency is
under the UFR setting
2. Incorrect country or Grid
setting
3. Detection circuit malfunction
1. Check the utility frequency on the inverter
terminal
2. Check country & Grid setting
3. Check the detection circuit inside the inverter
Grid Quality
Non-linear load in Grid and near
to inverter
Grid connection of inverter need to be far away
fromnon-linear load if necessary
HW Connect
Fail
1. Wrong connection in
AC plug
2. Detection circuit malfunction
1. Check the AC connection, must accords to
manual
2. Check the detection circuit inside the inverter
No Grid
1. AC breaker is OFF
2. Disconnect in AC plug
1. Switch on AC breaker
2. Check the connection in AC plug and make
sure it connects to inverter
AC Volt Low
1. Actual utility voltage is under
the UVR setting
2. Incorrect country or Grid
setting
3. Wrong connections in AC plug
4. One or more internal fuses are
broken
5. Detection circuit malfunction
1. Check the utility voltage connection to the
inverter terminal
2. Check country & Grid setting
3. Check the connection in AC plug
4. Replace fuses (FUC1-3) and check all
switching devices in boost & inverter stages
5. Check the detection circuit inside the inverter
AC Volt High
1. Actual utility voltage is over
the OVR setting
2. Utility voltage is over the Slow
OVR setting during operation
3. Incorrect country or Grid
setting
4. Detection circuit malfunction
1. Check the utility voltage on the inverter
terminal
2. Check the utility voltage on the inverter
terminal
3. Check country & Grid setting
4. Check the detection circuit inside the inverter

Table of Contents

Other manuals for Delta RPI-M20A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta RPI-M20A and is the answer not in the manual?

Delta RPI-M20A Specifications

General IconGeneral
BrandDelta
ModelRPI-M20A
CategoryInverter
LanguageEnglish

Related product manuals