22
!
!
5.3 DC Connection (from PV Array)
WARNING
When doing DC wiring, please choose the proper wiring by
connect to the correct polarity.
When doing DC wiring, please confirm that PV Array’s power
switch is off.
CAUTION
The connection number of PV Array, open circuit voltage and
power of String_1 and String _2 must be coherent.
The connection number of PV Array, open circuit voltage and
power of String _3 and String _4 must be coherent.
The maximum open circuit voltage of PV Array can not be higher
then 1000V.
The range of Vmpp of Input1 and Input2 shall be in 350~800 Vdc.
The device installed between PV Array and inverter must meet the
rating of voltage >1000 Vdc and > Short current.
The input power to the inverter is not recommended to exceed the
maximum rated power which show in table 5-3.
Table 5-4 Maximum rating of input power
Type of limit
RPI-M8
RPI-M10
RPI-M12
RPI-M15
Total input power
8.8 kW
11 kW
13.2 kW
16.5 kW
Input1 or Input2
5.9 kW
7.4 kW
8.8 kW
8.25 kW
Type of limit
RPI-M15A
RPI-M20
RPI-M20A
RPI-M30
Total input power
16.5 kW
22 kW
22 kW
32 kW
Input1 or Input2
8.25 kW
11 kW
11 kW
16 kW
Table 5-5 Cable size
Model
Current Rating
Wire size
Temperature
M8
DC 10A
2 - 3mm
2
/ 14 AWG
Meet UL 10070
M10/ M12
DC 20A
3 - 5mm
2
/ 12 AWG
Meet UL 10070
M15A/ M20A
DC 34A
5 - 6mm
2
/ 10 AWG
Meet UL 10070
M15/ M20/ M30
DC 34A
5 - 6mm
2
/ 10 AWG
Meet UL 10070

Table of Contents

Other manuals for Delta RPI-M20A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta RPI-M20A and is the answer not in the manual?

Delta RPI-M20A Specifications

General IconGeneral
BrandDelta
ModelRPI-M20A
CategoryInverter
LanguageEnglish

Related product manuals