Installation guide for solar inverters RPI M6A M8A M10A EU V5 EN 2022-08-15
Commissioning – Basic Settings
The inverter must be supplied with alternating current (grid) or direct current (solar modules) in order to
carry out commissioning.
1. Turn the AC/DC disconnector to the ON position.
Français
Deutsch
English
Select language
2. Use the and buttons to select English as the language and then
press the
ENT
button.
Thailand MEA
Thailand PEA
UK G59-3 230
CUSTOM
3. Use the and buttons to select your country or grid type and then
press the
ENT
button.
Yes / No
UK G59-3 230
set country:
Are you sure to
4. If the correct country is selected, use the and buttons to select Yes
and the press the
ENT
button.
To change the selection, press the
ESC
button.
ID=001
Setting ID:
NOTE
If multiple inverters are connected to the PV system, a di󰀨erent inverter ID must
set for each inverter. The inverter ID is used, for example, by monitoring systems
to uniquely identify each inverter.
5. Use the and buttons to set the individual digits and then press the
ENT
button.
Yes / No
ID: 1
Are you sure to set
6. Check that the correct inverter ID is set.
If the correct inverter ID is selected, use the and buttons to select
Yes and the press the
ENT
button.
To change the selection, press the
ESC
button.
Yes / No
Set Wi-Fi ON
7. Use the and buttons to switch the Wi-Fi on or o󰀨 and then press the
ENT
button. Use the and buttons to select Yes and the press the
ENT
button. To change the selection, press the
ESC
button.
10.Sep 2019 14:55
8. Use the and buttons to congure the value and then press the
ENT
button.
Repeat the procedure for the other settings.
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2019 15:32
þ
The basic settings have now been congured. The default menu is displayed.
The inverter starts a self-test lasting approx. 2 minutes. The remaining time
is shown on the display.