Installation guide for solar inverters RPI M6A M8A M10A EU V5 EN 2022-08-15
External power-o (EPO)
E-Today: 0kWh
Power: 0W
Status: On Grid
12.Sep 2019 15:32
1. If the default information is displayed, press the
ESC
button to open the main
menu. Otherwise, press the
ESC
button repeatedly until the main menu is
displayed.
General Settings
Install Settings
2. Use the and buttons to select the Install Settings entry and then
press the
ENT
button.
energy production
Adj. would effect
3. This function is protected with password 5555.
Use the and buttons to set the individual numerals.
Press the
ENT
button to conrm a numeral.
Grid Settings
DC Injection
Dry Cont. Disabled
RCMU: ON
EPO: Normal Close
4. Use the buttons and to select the entry EPO and press the
ENT
but-
ton.
5. Use the and buttons to select an option and then press the
ENT
button.
Available options
Nrm. open (normally open): The relay operates as a normally open device.
Nrm. closed (normally closed): The relay operates as a normally closed device.
Active power limitation
Change this setting only after consultation
with Delta customer service.
To change this setting, you need a speci-
al password that you receive from Delta
customer service. You can nd the contact
information on the back of this document.
E-Today: 0kWh
Power: 0W
Status: On Grid
12.Sep 2019 15:32
1. If the default information is displayed, press the
ESC
button to open the main
menu. Otherwise, press the
ESC
button repeatedly until the main menu is
displayed.
General Settings
Install Settings
2. Use the and buttons to select the Install Settings entry and then
press the
ENT
button.
energy production
Adj. would effect
3. Enter the password provided by Delta customer service. Use the and
buttons to set the individual numerals.
Press the
ENT
button to conrm a numeral.
AC Connection: 3P3W
EPO: Normal Close
Anti-islanding: ON
Max. Power: 10000W
Return to Factory
4. Use the and buttons to select Max. Power and then press the
ENT
button.
5. Use the and buttons to congure a value and then press the
ENT
button.
Commissioning – further settings (optional)