Chapter 11 Summary of Parameter SettingsME300
11-31
08 High-function PID Parameters
Pr. Explanation Settings Default
08-00
Terminal selection of
PID feedback
0: No function
1: Negative PID feedback: by analog input (Pr.03-00)
4: Positive PID feedback: by analog input (Pr.03-00)
7: Negative PID feedback:
by communication protocol
8: Positive PID feedback:
by communication protocol
0
08-01 Proportional gain (P)
0.0–500.0 (When Pr.08-23 bit1 = 0)
0.00–500.00 (When Pr.08-23 bit1 = 1)
1.00
08-02 Integral time (I) 0.00–100.00 sec. 1.00
08-03 Differential time (D) 0.00–1.00 sec. 0.00
08-04
Upper limit of integral
control
0.0–100.0% 100.0
08-05
PID output command limit
(positive limit)
0.0–100.0% 100.0
08-06
PID feedback value by
communication protocol
-200.00–200.00% 0.00
08-07 PID delay time 0.0–2.5 sec. 0.0
08-08
Feedback signal detection
time
0.0–3600.0 sec. 0.0
08-09
Feedback signal fault
treatment
0: Warn and continue operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: Warn and operate at last frequency
0
08-10 Sleep frequency 0.00–599.00 Hz 0.00
08-11 Wake-up frequency 0.00–599.00 Hz 0.00
08-12 Sleep time 0.0–6000.0 sec. 0.0
08-13 PID deviation level 1.0–50.0% 10.0
08-14 PID deviation time 0.1–300.0 sec. 5.0
08-15 PID feedback filter time 0.1–300.0 sec. 5.0
08-16
PID compensation
selection
0: Parameter setting
1: Analog input
0
08-17 PID compensation -100.0–100.0% 0
08-18
Sleep mode function
setting
0: Refer to PID output command
1: Refer to PID feedback signal
0
08-19 Wake-up integral limit 0.0–200.0% 50.0
08-20 PID mode selection
0: Serial connection
1: Parallel connection
0
08-21
Enable PID to change the
operation direction
0: Operating direction can be changed
1: Operating direction cannot be changed
0