Chapter 12 Description of Parameter SettingsME300
12.1-12-5
Default: 1
Settings 0: By pump’s ID #
1: By the running time.
0: By pump ID#, (1 2 3 4 1)
1: By the shortest running time
Running Time of Multi-pump under Alternative Operation
Default: 60.0
Settings 0.0–360.0 sec.
This parameter only applies for the master pump.
The assigned value (setting value) of time to switch between master pump and slave pump.
Assign the Setting for Pr.08-13 PID Feedback Level
Default: 0
Settings 0: Use the current setting (default), verify if any error by checking feedback
deviation.
1: Set low water pressure percentage (%), verify if any error by checking
physical quantity value’s feedback.
When the pressure sensor is set to be 10 kg, Pr.12-16=0 and Pr.08-13=10.0% (it means
deviation = 1 kg), and if the target value is 3 kg and the feedback < 2 kg at this time, the motor
drive follows the setting at Pr.08-62.
When the pressure sensor is set to be 10 kg, Pr.12-16=1 and Pr.08-13=10.0% (it means the
physical quantity = 1 kg), and if the target value =3 kg and the feedback < 1kg at this time, the
motor drive follows the setting at Pr.08-62.
Simple Positioning Stop Frequency 0
Default: 0.00
Settings 0.00–599.00 Hz
Simple Positioning Stop Frequency 1
Default: 5.00
Settings 0.00–599.00 Hz
Simple Positioning Stop Frequency 2
Default: 10.00
Settings 0.00–599.00 Hz
Simple Positioning Stop Frequency 3
Default: 20.00
Settings 0.00–599.00 Hz
Simple Positioning Stop Frequency 4
Default: 30.00
Settings 0.00–599.00 Hz
Simple Positioning Stop Frequency 5