Chapter 11 Summary of Parameter SettingsME300
11-37
12 Function Parameters
Pr.
Explanation Settings Default
12-00 Set point deviation level 0–100% 0
12-01
Detection time of set point
deviation level
1–9999 sec. 10
12-02
Offset level of liquid
leakage
0–50% 0
12-03
Liquid leakage change
detection
0: Disable
0–100%
0
12-04
Time setting for liquid
leakage change
0: Disable
0.1–10.0 sec.
0.5
12-05 Multi-pump control mode
00: Disable
01: Fixed time circulation (alternative operation)
02: Fixed quantity control
(multi-pump operating at constant pressure)
0
12-07
Multi-pump’s fixed time
circulation period
1–65535 (minute) 60
12-08
Frequency to start
switching pumps
0.00 Hz–FMAX 60.00
12-09
Time detected when
pump reaches the
starting frequency
0.0–3600.0 sec. 1.0
12-10
Frequency to stop
switching pumps
0.00 Hz–FMAX 48.00
12-11
Time detected when
pump reaches the
stopping frequency
0.0–3600.0 sec. 1.0
12-12
Pump’s frequency at
time-out
(disconnection)
0.00–FMAX 0.00
12-13 Pump’s error treatment
bit0: whether to switch to an alternative pump when
operation pump error occurred.
0: Stop all pump actions.
1: Switch to an alternative pump.
bit1: Standby or stop after resetting from error.
0: Standby after reset.
1: Stop after reset.
bit2: To run a pump or not when an error is occurred.
0: Do not start.
1: Select an alternative pump.
1