Chapter 12 Description of Parameter SettingsME300
12.1-13-3
Group setting 05: Conveyor
The following table lists the relevant conveyor setting application parameters.
Pr. Explanation Settings
00-11 Speed control mode 0 (VF)
00-16 Load selection 0 (Normal load)
00-20 Master frequency command source (AUTO) 2 (External analog input)
00-21 Operation command source (AUTO) 1 (External terminals)
01-00 Motor 1 maximum operation frequency Default setting
01-01 Motor 1 output frequency Default setting
01-02 Motor 1 output voltage Default setting
01-03 Motor 1 mid-point frequency 1 Default setting
01-04 Motor 1 mid-point voltage 1 Default setting
01-05 Motor 1 mid-point frequency 2 Default setting
01-06 Motor 1 mid-point voltage 2 Default setting
01-07 Motor 1 minimum output frequency Default setting
01-08 Motor 1 minimum output voltage of motor 1 Default setting
01-12 Acceleration time 1 10 (s)
01-13 Deceleration time 1 10 (s)
Group setting 07: Packing
The following table lists the relevant packing setting application parameters.
Pr. Explanation Settings
00-11 Speed control mode 0 (VF)
00-20 Master frequency command source (AUTO) 0 (Digital keypad)
00-21 Operation command source (AUTO) 2 (RS-485 Communication input)
02-00 Two-wire / Three-wire operation control
1 (two-wire mode 1, power on for
operation control (M1: FWD /
STOP, M2: REV / STOP))
01-00 Motor 1 maximum operation frequency Default setting
01-01 Motor 1 output frequency Default setting
01-02 Motor 1 output voltage Default setting
01-03 Motor 1 mid-point frequency 1 Default setting
01-04 Motor 1 mid-point voltage 1 Default setting
01-05 Motor 1 mid-point frequency 2 Default setting
01-06 Motor 1 mid-point voltage 2 Default setting
01-07 Motor 1 minimum output frequency Default setting
01-08 Motor 1 minimum output voltage Default setting
01-12 Acceleration time 1 10 (s)
01-13 Deceleration time 1 10 (s)
01-24 S-curve acceleration begin time 1 Default setting