Chapter 12 Description of Parameter SettingsME300
12.1-06-16
Detection Time for Output Phase Loss
Default: 0.500
Settings 0.000–65.535 sec.
Current Detection Level for Output Phase Loss
Default: 1.00
Settings 0.00–100.00%
DC Brake Time for Output Phase Loss
Default: 0.000
Settings 0.000–65.535 sec.
Setting Pr.06-48 to 0 disables the OPHL detection function.
Status 1: The drive is in operation
When any phase is less than the Pr.06-47 setting, and exceeds the Pr.06-46 setting time, the
drive executes according to the Pr.06-45 setting.
Status 2: The drive is in STOP; Pr.06-48 = 0; Pr.07-02 ≠ 0
After the drive starts, the DC brake operates according to Pr.07-01 and Pr.07-02. During this
period, OPHL detection is not active. After the DC brake action is completed, the drive starts to
run, and enables the OPHL protection as mentioned above for status 1.