EasyManuals Logo
Home>Delta>DC Drives>VFD17AME43ANNAA

Delta VFD17AME43ANNAA User Manual

Delta VFD17AME43ANNAA
403 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #40 background imageLoading...
Page #40 background image
Chapter 5 Main Circuit TerminalsME300
5-9
Frame D
If you install at Ta 50°C above environment, use copper wires that have a voltage rating of
600 V and are temperature resistant to 90°C or above.
If you install at Ta 50°C environment, use copper wires that have a voltage rating of 600 V
and are temperature resistant to 75°C or 90°C.
For VFD25AME23ANNAA, VFD25AME23ANSAA:
If you install at Ta 45°C above environment, use copper wires that have a voltage rating of
600 V and are temperature resistant to 90°C or above.
To be UL installation compliant, you must use copper wires when installing. The wire gauge
is based on a temperature resistance of 75°C, in accordance with UL requirements and
recommendations.
Do not reduce the wire gauge when using high-temperature resistant wires.
Models
Main Circuit Terminals
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3,
DC-, DC+/+1, +2/B1, B2
Terminals
Max. Wire
Gauge
Min. Wire
Gauge
Screw &
Torque
(±10%)
Max. Wire
Gauge
Min. Wire
Gauge
Screw &
Torque
(±10%)
VFD25AME23ANNAA
10 mm
2
[8 AWG]
10 mm
2
[8 AWG]
M4
20 Kg-cm
[17.4 lb-in.]
[1.96 Nm]
10 mm
2
[8 AWG]
10 mm
2
[8 AWG]
M4
20 Kg-cm
[17.4 lb-in.]
[1.96 Nm]
VFD25AME23ANSAA
VFD13AME43ANNAA
6 mm
2
[10 AWG]
6 mm
2
[10 AWG]
6 mm
2
[10 AWG]
VFD13AME43AFNAA
VFD13AME43ANSAA
VFD13AME43AFSAA
VFD17AME43ANNAA
10 mm
2
[8 AWG]
10 mm
2
[8 AWG]
10 mm
2
[8 AWG]
VFD17AME43AFNAA
VFD17AME43ANSAA
VFD17AME43AFSAA

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD17AME43ANNAA and is the answer not in the manual?

Delta VFD17AME43ANNAA Specifications

General IconGeneral
BrandDelta
ModelVFD17AME43ANNAA
CategoryDC Drives
LanguageEnglish

Related product manuals