Chapter 11 Summary of Parameter SettingsME300
11-39
Pr.
Explanation Settings Default
12-35
Delay time of simple
positioning stop 7
0.00–600.00 sec. 0.00
12-40 Automatic operation mode
0: Disable operation
1: Execute one program cycle
2: Continuously execute program cycles
3: Execute one program cycle step by step
4: Continuously execute one program cycle step by step
5: Disable automatic operation, but the direction setting
at multi-step speed 1 to 7 are effective
0
12-41
PLC program running
direction mode
bit 0–bit 7 (0: FWD RUN, 1: REV RUN)
bit 0: Direction of auto-operation’s main speed
bit 1: Direction of 1
st
speed for Pr.04-00
bit 2: Direction of 2
nd
speed for Pr.04-01
bit 3: Direction of 2
nd
speed for Pr.04-02
bit 4: Direction of 2
nd
speed for Pr.04-03
bit 5: Direction of 2
nd
speed for Pr.04-04
bit 6: Direction of 2
nd
speed for Pr.04-05
bit 7: Direction of 2
nd
speed for Pr.04-06
0
12-42
Main frequency time
setting
0
65500 sec.
0
12-43 1
st
speed time setting
0
65500 sec.
0
12-44 2
nd
speed time setting
0
65500 sec.
0
12-45 3
rd
speed time setting
0
65500 sec.
0
12-46 4
th
speed time setting
0
65500 sec.
0
12-47 5
th
speed time setting
0
65500 sec.
0
12-48 6
th
speed time setting
0
65500 sec.
0
12-49 7
th
speed time setting
0
65500 sec.
0