Chapter 12 Description of Parameter SettingsME300
12.1-02-17
Output Frequency Setting for Multi-function Output Terminal
Default: 0.00
Settings 0.00–599.00 Hz
Multi-function Output Terminal: Function 42: Brake Frequency Check Point
Default: 0.00
Settings 0.00–599.00 Hz
You can use Pr.02-34 with Pr.02-58 for the crane function. You can choose the crane action # 42
to set the multi-function outputs Pr.02-13 and Pr.02-16.
When the output frequency of the drive is higher than the setting for Pr.02-34 frequency level
(≥ Pr.02-34), choose # 42 to set the multi-function output terminal.
When the output frequency is lower than the setting for Pr.02-58 (< Pr.02-58), choose # 42 to
disable the multi-function output terminal.
Crane application example:
It is recommended that you use this with the Dwell function as shown in the following diagram:
External Operation Control Selection after Reset and Activate
Default: 0
Settings 0: Disable
1: Drive runs if the RUN command remains after reset or reboot.
Set value as 1:
Status 1: After the drive is powered on and the external terminal for RUN stays ON, the drive
runs.