Chapter 12 Description of Parameter SettingsME300
12.1-00-1
Chapter 12 Description of Parameter Settings
12-1 Description of Parameter Settings
00 Drive Parameters
You can set this parameter during operation.
Identity Code of the AC Motor Drive
Default: #.#
Settings Read Only
Display AC Motor Drive Rated Current
Default: #.#
Settings Read Only
Pr.00-00 displays the identity code of the AC motor drive. Use the following specification table to
check if Pr.00-01 setting is the rated current of the AC motor drive. Pr.00-01 corresponds to the
identity code of the motor.
The default is the rated current for heavy duty. Set Pr.00-16 to 0 to display the rated current for
normal duty.
Series 115V Series: One-Phase 230V Series: One-Phase
Frame
A B C A/B B C
kW 0.1 0.2 0.4 0.75 0.1 0.2 0.4 0.75 1.5 2.2
HP 0.125 0.25 0.5 1 0.125 0.25 0.5 1 2 3
Identity Code 101 102 103 104 301 302 303 304 305 306
Rated Current for
Heavy Duty
0.8 1.6 2.5 4.8 0.8 1.6 2.8 4.8 7.5 11
Rated Current for
Normal Duty
1 1.8 2.7 5.5 1 1.8 3.2 5 8.5 12.5
230V Series: Three-Phase
Frame
A B C D E F
kW 0.1 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15
HP 0.125 0.25 0.5 1 2 3 5 7.5 10 15 20
Identity Code 201 202 203 204 205 206 207 208 209 210 211
Rated Current for
Heavy Duty
0.8 1.6 2.8 4.8 7.5 11 17 25 33 49 65
Rated Current for
Normal Duty
1 1.8 3.2 5 8 12.5 19.5 27 36 51 69
460V Series: Three-Phase
Frame
A/B
B C D E F
kW 0.4 0.75 1.5 2.2 3 3.7 5.5 7.5 11 15 18.5 22
HP 0.5 1 2 3 4 5 7.5 10 15 20 25 30
Identity Code 403 404 405 406 482 407 408 409 410 411 412 413
Rated Current for
Heavy Duty
1.5 2.7 4.2 5.5 7.3 9 13 17 25 32 38 45
Rated Current for
Normal Duty
1.8 3 4.6 6.5 8 10.5 15.7 20.5 28 36 41.5 49