Chapter 12 Description of Parameter SettingsME300
12.1-06-5
Accel./Decel. Time Selection for Stall Prevention at Constant Speed
Default: 0
Settings 0: By current acceleration / deceleration time
1: By the 1
st
acceleration / deceleration time
2: By the 2
nd
acceleration / deceleration time
3: By the 3
rd
acceleration / deceleration time
4: By the 4
th
acceleration / deceleration time
5: By auto-acceleration / auto-deceleration
Sets the acceleration / deceleration time selection when stall prevention occurs at constant
speed.
Over-torque Detection Selection (Motor 1)
Default: 0
Settings 0: No function
1: Continue operation after over-torque detection during constant speed
operation
2: Stop after over-torque detection during constant speed operation
3: Continue operation after over-torque detection during RUN
4: Stop after over-torque detection during RUN
Over-torque Detection Selection (Motor 2)
Default: 0
Settings 0: No function
1: Continue operation after over-torque detection during constant speed
operation
: Stop after over-torque detection during constant speed operation
3: Continue operation after over-torque detection during RUN
: Stop after over-torque detection during RUN
When you set Pr.06-06 and Pr.06-09 to 1 or 3, a warning message displays but there is no error
record.
When you set Pr.06-06 and Pr.06-09 to 2 or 4, a warning message displays and there is an error
record.
Over-torque Detection Level (Motor 1)
Default: 120
Settings 10–250% (100% corresponds to the rated current of the drive)
Over-torque Detection Time (Motor 1)
Default: 0.1
Settings 0.0–60.0 sec.