Chapter 12 Description of Parameter SettingsME300
12.1-02-3
19: Digital up command
20: Digital down command
21: PID function disabled
22: Clear the counter
23: Input the counter value (MI4)
24: FWD JOG command
25: REV JOG command
28: Emergency stop (EF1)
29: Signal confirmation for Y-connection
30: Signal confirmation for Δ-connection
38: Disable write EEPROM function
40: Force coasting to stop
41: HAND switch
42: AUTO switch
49: Enable Drive
50: Master dEb input
56: Local / Remote selection
69: Auto-activate preheating function
71: Disable PID function, force PID output return to 0
72: Disable PID function, retain the output value before disabled
73: Force PID integral gain return to 0, disable integral
74: Reverse PID feedback
83: Multi-motors (IM) selection bit 0
94: Programmable AUTO RUN
95: Pausing AUTO RUN
97: Multi-pumps switch by Hand / Auto mode
98: Simple positioning stop by forward limit
99: Simple positioning stop by reverse limit
This parameter selects the functions for each multi-function terminal.
When Pr.02-00 = 0, you can set multi-function options with the multi-function input terminals MI1,
MI2.
When Pr.02-00 ≠ 0, the multi-function input terminals MI1, MI2 work in accordance with the
setting values for Pr.02-00.
Example:
If Pr.02-00 = 1: multi-function input terminal MI1 = FWD / STOP,
multi-function input terminal MI2 = REV / STOP.
If Pr.02-00 = 2: multi-function input terminal MI1 = RUN / STOP,
multi-function input terminal MI2 = FWD / REV.
If Pr.02-00 is set to three-wire operation control, terminal MI3 is for the STOP contact. The function
set previously for this terminal is automatically invalid.
Summary of function settings
Take the normally opened contact (N.O.) for example, ON: contact is closed, OFF: contact is open.