Chapter 12 Description of Parameter SettingsME300
12.1-08-6
Parallel connection
Feedback Signal Detection Time
Default: 0.0
Settings 0.0–3600.0 sec.
Pr.08-08 is valid only for Pr.03-28=2 (4–20 mA).
This parameter sets the detection time for abnormal PID signal feedback. Setting the detection
time to 0.0 disables the detection function.
Feedback Signal Fault Treatment
Default: 0
Settings 0: Warn and continue operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: Warn and operate at last frequency
This parameter is valid only for Pr.03-28=2 (4–20 mA)..
The AC motor drive acts when the analog PID feedback is abnormal.
Sleep Frequency
Default: 0.00
Settings 0.00–599.00 Hz
Determines the sleep frequency, and if the sleep time and the wake-up frequency are enabled or
disabled.
Pr.08-10 = 0: Disabled
Pr.08-10 = ≠ 0: Enabled