Chapter 12 Description of Parameter SettingsME300
12.1-13-1
13 Macro / User-Defined Macro
Application Selection
Default: 00
Settings 00: Disabled
01: User-Defined parameter
03: Fan
04: Pump
05: Conveyor
07: Packing
Note: after you select the macro, some of the default values adjust automatically according to the
application selection.
Group setting 03: Fan
The following table lists the relevant fan setting application parameters.
Pr. Explanation Settings
00-11 Speed control mode 0 (VF)
00-16 Load selection 0 (Normal load)
00-17 Carrier frequency Default setting
00-20 Master frequency command source (AUTO) 2 (External analog input)
00-21 Operation command source (AUTO) 1 (External terminals)
00-22 Stop method 1 (Coast to stop)
00-23 Control of motor direction 1 (Disable reverse)
00-30 Master frequency command source (HAND) 0 (Digital keypad)
00-31 Operation command source (HAND) 0 (Digital keypad)
01-00 Motor 1 maximum operation frequency Default setting
01-01 Motor 1 output frequency Default setting
01-02 Motor 1 output voltage Default setting
01-03 Motor 1 mid-point frequency 1 Default setting
01-04 Motor 1 mid-point voltage 1 Default setting
01-05 Motor 1 mid-point frequency 2 Default setting
01-06 Motor 1 mid-point voltage 2 Default setting
01-07 Motor 1 minimum output frequency Default setting
01-08 Motor 1 minimum output voltage Default setting
01-10 Output frequency upper limit 50 (Hz)
01-11 Output frequency lower limit 35 (Hz)
01-12 Acceleration time 1 15 (s)
01-13 Deceleration time 1 15 (s)
01-43 V/F curve selection 2 (Second V/F curve)
02-05 Multi-function input command 5 (MI5)
15: Rotating speed command from
AVI
02-16 Multi-function output 2 (MO1) 11 (Malfunction indication)