EasyManuals Logo
Home>Eaton>UPS>9135

Eaton 9135 User Manual

Eaton 9135
58 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #45 background imageLoading...
Page #45 background image
Additional Features
Eaton 9135 5000/6000 VA UPS User’s Guide 164201726—Rev 4 www.eaton.com/powerquality 39
Relay Port
When the status is active, the contact between the common (Pin 5) and the relevant information pin is closed.
Output relay specifications:
l
Voltage: 48 Vdc maximum
l
Current: 2A maximum
l
Power: 62.5 VA, 30W
Example: for 48 Vdc, Imax=625 mA
Figure 32 identifies the cable pins and Table 11 describes the pin functions.
Figure 32. Communication Port
Table 11. Communication Port Pin Assignment
Pin Number Function
1, 2 Not used
3 Remote Power-off signal (527 Vdc, 10 mA max)
4 Operation on mains (not on battery)
5 User common
6 Operation on automatic bypass
7 Low Battery
8 Load protected
9 Operation on battery
NOTE Normally-open (NO)
Normally-closed (NC)
Common
NC NO NO NO NO
7
8
6
9
3
5
421