104 Eaton 9355 UPS (10/15 kVA) User’s Guide 164201594—Rev H0
Table 16. Environmental and Safety Specifications
Operating Temperature
50°F to 104°F (10°C to 40°C)
Optimal battery performance: 77°F (25°C)
Transit Temperature
-13°F to 131°F (-25°C to 55°C)
Storage Temperature
32°F to 77°F (0°C to 25°C)
Recommended battery storage: 59°F to 77°F (15°C to 25°C)
Ventilation
Front air intake, forced air, two fans, positive pressurization, temperature UPS-monitored
Altitude
9,843 ft (3,000m) operating without derating 32,810 ft (10,000m) during transportation
Relative Humidity 5 95% noncondensing
Audible Noise
<56 dBA at 1 meter distance, typical loads<62 dBA for heavy load, high ambient or high
altitude, on battery
Surge Suppression
ANSI C62.41 Category B3, IEC 61000-4-5
Safety Conformance
UL1778 5th Edition, CSA C22.2 No. 107.3-14, NOM-NYCE
Agency Markings
cULus, NOM-NYCE
EMC (Class A) 47 CFR Part 15/ICES-003 Class A
Table 17. Technical Specifications
Technology
Online, double conversion topology with static bypass switch and 3 position maintenance
bypass switch. Frequency independent operation.
Input Voltage Range
75/130 144/249 Vac per phase
Input Power Factor
>0.99 at full load nominal line conditions
Input Rated Voltage
120/208 or 127/220 Vac three-phase
Isolation Transformer Input
Voltage Range
480V or 600V ±20%60 Hz only
Input Frequency Range
45 65 Hz
Input Rated Frequency
50/60-Hz selectable, auto configuring
Output Voltage Regulation
±1% static, Phase to Neutral±2% static, Phase to Phase±5% dynamic at 100% resistive
load change Response time <1 ms
Output Voltage Distortion
<2% THD linear load<5% THD non linear load
Output Frequency
50/60-Hz selectable or auto configuring
Output Frequency Regulation
Synchronization to line
Output Overload
101 110% for 10 minutes 111 125% for 60 seconds 126 149% for 5 seconds>150% for 300
milliseconds
Product Specifications