Eaton 93E UPS 15-80 kVA (380/400/415 V) Installation and Operation Manual
© Eaton Corporation plc 2015. All rights reserved. Revision: 001
Document ID: 614-01975-00
75 (133)
Figure 30.Path of current through the UPS in the standard normal mode
converter
breaker
relay
contactor
The battery converter derives its input from the regulated DC output of
the rectifier and provides either a boosted or bucked regulated DC
voltage charge current to the battery. The battery is always connected to
the UPS and ready to support the inverter should the utility input
become unavailable.
The inverter produces a 3-phase AC output to the customer's load
without the use of a transformer. The inverter derives regulated DC from
the rectifier and uses IGBT devices and pulse-width modulation (PWM)