UPS Maintenance
Eaton 93PM UPS (20–50 kW, 480V Four Wire – 50 kW Frame) Installation and Operation Manual P-164000540—Rev 4 www.eaton.com/powerquality 8-3
Figure 8-1. Air Filter Location
8.2.3 PERIODIC Maintenance
Periodic inspections of the UPS should be made to determine if components, wiring, and connections exhibit
evidence of overheating. Particular attention should be given to the compression lug connections. Maintenance
procedures should specify that the compression lug connections be retorqued to values listed in this manual.
8.2.4 ANNUAL Maintenance
Annual preventive maintenance should be performed only by authorized service personnel familiar with
maintenance and servicing of the UPS system. Contact an Eaton service representative for more information
about service offerings.
8.2.5 BATTERY Maintenance
Contact an Eaton service representative for battery maintenance. Battery replacement and maintenance should
be performed only by authorized service personnel.
Air Filter

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton 93PM UPS and is the answer not in the manual?

Eaton 93PM UPS Specifications

General IconGeneral
TopologyDouble conversion online
Frequency50/60 Hz
Operating Temperature0°C to 40°C
EfficiencyUp to 97% in double conversion mode
Input Voltage208/220/400/480V
Output Voltage208, 220, 380, 400, 415, 480 V (depending on model)
Battery TypeVRLA
Form FactorTower
Power Factor0.9
Relative Humidity0% to 95% non-condensing
Communication PortsUSB, RS232, SNMP
DimensionsVaries by model
WeightVaries by model
Storage Temperature-15 to 50 °C (5 to 122 °F)
Audible Noise<65 dB at 1 meter

Related product manuals