EasyManuals Logo
Home>Eaton>UPS>93PM UPS

Eaton 93PM UPS User Manual

Eaton 93PM UPS
146 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #82 background image
UPS System Installation
4-32 Eaton 93PM UPS (20–50 kW, 480V Four Wire – 50 kW Frame) Installation and Operation Manual P-164000540—Rev 4 www.eaton.com/powerquality
Figure 4-26. Normally-Open REPO Switch Wiring
Figure 4-27. Normally-Closed REPO Switch Wiring
Table 4-7. Normally-Open REPO Connections and Wire Terminations
From REPO Station
Switch Contact
Block
(Either Block)
UPS REPO
Terminal Name Description
Recommended
Minimum Wire
Size
Size of Wire
Termination
Tightening
Torque
3 NO 3 EPO_A
Input: Normally-open dry contact used to activate
UPS EPO from a remote switch
Twisted Pair Wires
#18 AWG
#1630 AWG
2lbin
(0.22-0.25 Nm)
4 NO 4 EPO_B
3
1
2
4
3
4
REPO
Switch
(NO)
Twisted
Wires
REPO TB
NOTE REPO switch rating is 24 Vdc, 1A minimum.
NOTE The REPO switch must be a latching-type switch not tied to any other circuits.
Table 4-8. Normally-Closed REPO Connections and Wire Terminations
From REPO Station
Switch Contact
Block
(Either Block)
UPS REPO
Terminal Name Description
Recommended
Minimum Wire
Size
Size of Wire
Termination
Tightening
Torque
3 NO 1 EPO_A_B
Input: Normally-closed dry contact used to activate
UPS EPO from a remote switch
Twisted Pair Wires
#18 AWG
#1630 AWG
2lbin
(0.22-0.25 Nm)
4 NO 2 GND-ISO
3
1
2
4
1
2
REPO
Switch
(NC)
Twisted
Wires
REPO TB
NOTE REPO switch rating is 24 Vdc, 1A minimum.
NOTE The REPO switch must be a latching-type switch not tied to any other circuits.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton 93PM UPS and is the answer not in the manual?

Eaton 93PM UPS Specifications

General IconGeneral
BrandEaton
Model93PM UPS
CategoryUPS
LanguageEnglish

Related product manuals