1 - Remove the terminal block cover
(5 screws),
2 - Remove the bridge connected
between L2 and L1,
3 - Insert the Normal AC cable through
the cable gland,
4 - Connect the 5 wires to the Normal
AC terminal block,
Always connect the earthing
wire rst.
5 - Insert the Output cable to the load
through the Output cable gland,
6 - Connect the 3 wires to the output
terminal block,
7 - Insert the Bypass cable through the
cable gland,
8 - Connect the 3 wires to the Bypass
AC terminal block,
9 - Refit the terminal block cover and
tighten the cable glands,
10 - Secure the junction Input/Output
box to the rear of the power module
by means of the 3 screws.
UPS with separate Normal and Bypass AC sources
2. Installation
1
5
2
4
3
9
6
7
1
1
1
9
9
9
10
Card Settings
RS232 Download
66074
UPS
data
Reset
100 10
1 2
ON
ETHERNET
IP=
MAC=00E0D8FF855E
NORMAL
φ
Rectifier Input
L2
L1
L1
Bypass Input
N2
L2
N1
L3
Output
N
L
Rectifier Input
L2
L1
L1
Bypass Input
N2
L2
N1
L3
Output
N
L
Rectifier Inp
ut
L2
L1
L1
Bypass Input
N2
L2
N1
L3
Output
N
L
1
8
9
10
10

Table of Contents