3. Operation
Personnalisation batterie
Use EXIT key when set up is completed. z
These parameters are only adjustable if z UPS is OFF.
Access to the personalisation through external software
Insert the z Solution-Pac CD ROM in your CD drive.
At the first Navigator Screen, select "Installation" and follow the instructions to install z Personal
Solution-Pac for Windows.
If nothing appears, launch startup.exe z
Then go to "Advanced settings" and "UPS settings". z
Please note that the Linux/Unix/MacOS versions of Personal Solution-Pac do not include this feature.
3.2 Final start up sequence
Press the ON button more than 3 seconds. z
After UPS internal test sequence, the green LED z
13
goes on.
During the restart, if the Bypass AC source is out of tolerance, the UPS will generate an output 10 ms calibrated
break.
ON/OFF features
Function Factory setting Options Comments
Cold start
Disabled Enabled Start on battery.
Forced reboot Enabled Disabled
Enables automatic restart of the system
even if normal AC source is restored before
the end of the shutdown sequence.
Automatic restart Enabled Disabled
UPS restarts automatically
when normal AC source is restored.
Sleep mode
Disabled
Enabled
Automatic shudown on battery if output
load level < 10%.
UPS ON/OFF by software Enabled Disabled
Enables consideration of shutdown
or restart orders from software to be
authorized.
Function Factory setting Options Comments
Battery test Every week No test / daily / monthly
Low battery signal 20 %
0 to 100 %
1% increment.
Run time choice UPS reads # of battery
modules connected
From 50 to 400 Ah
Requires EX RT CLA if using
options (see section 1.4
"Battery extensions").
Battery deep discharge
protection
Enabled Disabled If disabled, lost of EATON
warranty.