34007724EN/AD - Page 23
Frequency converter
1 - Remove the terminal block cover
(5 screws),
2 - Remove the bridge connected
between L2 and L1,
3 - Insert the Normal AC cable through
the cable gland,
4 - Connect the 5 wires to the Normal
AC terminal block,
Always connect the earthing
wire rst.
5 - Insert the Output cable suppling the
load through the Output cable gland,
6 - Connect the 3 wires to output
terminal block,
Do not connect anything to the
Bypass AC terminal block,
7 - Refit the terminal block cover and
tighten the cable glands,
8 - Secure the junction Input/Output
box to the rear of the power module
by means of the 3 screws.
1
5
3
6
4
7
2
1
1
1
7
7
2. Installation
8
Rectifier Input
L2
L1
L1
Bypass Input
N2
L2
N1
L3
Output
N
L
Rectifier Input
L2
L1
L1
Bypass Input
N2
L2
N1
L3
Output
N
L
Card Settings
RS232 Download
66074
UPS
data
Reset
100 10
1 2
ON
ETHERNET
IP=
MAC=00E0D8FF855E
NORMAL
φ
Rectifier Input
L2
L1
L1
Bypass Input
N2
L2
N1
L3
Output
N
L
1
7
7
8
8

Table of Contents

Other manuals for Eaton EX RT 5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton EX RT 5 and is the answer not in the manual?

Eaton EX RT 5 Specifications

General IconGeneral
BrandEaton
ModelEX RT 5
CategoryUPS
LanguageEnglish

Related product manuals