EXAMPLE 2:
Comp Voltage 115.0
Band 108.0-112.0
Using Func 51-55
Compensated Voltage = 115.0
Rev. Set Voltage = 110.0 V
Rev. Bandwidth = 4.0 V
Control experiencing reverse power flow as indicated by
reference to FC 51-55
Load voltage
When the *Load Voltage key is pressed, the LCD will
display the following information:
The first line displays a live representation of the load
voltage. The load voltage is also available at FC 6.
The second line displays the voltage limits to be applied
by the Voltage-Limiting feature (see Section6: Control
Features: Voltage limiter). If a voltage range is displayed,
a high and low limit is enabled. A single value implies that
only the high limit is active.
The Voltage Limiter High and Voltage Limiter Low LEDs are
used to indicate the voltage limiter is active.
EXAMPLE 1:
Load Voltage 115.0
Limiter 119.0-121.0
Load Voltage = 115.0 V
Voltage-Limiting Mode = High and Low Limits Active
High Voltage Limit = 121.0 V
Low Voltage Limit = 119.0 V
EXAMPLE 2:
Load Voltage 115.0
Limiter 121.0
Load Voltage = 115.0 V
Voltage-Limiting Mode = Only High Limit Active
High Voltage Limit = 121.0 V
EXAMPLE 3:
Load Voltage 115.0
Limiter Off
Load Voltage = 115.0 V
Voltage-Limiting Mode = Off
Load current
When the *Load Current key is pressed, the LCD will
display the following information:
The first line displays a live representation of the load
current. The load current is also available at FC 9. This line
also includes an abbreviation of the power flow direction:
"Fwd" corresponds to Forward, "Rev" corresponds to
Reverse.
The second line displays the current threshold. This is the
point below which the control enters an indeterminate
current flow state. See Section6: Control Features:
Reverse power operation in this manual for more
information on the current threshold. The current threshold
is the product of the CT Primary Rating, and the Reverse
Threshold percentage.
144
INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS MN225003EN April 2018
CL-7 Voltage Regulator Control

Table of Contents

Other manuals for Eaton QD5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton QD5 and is the answer not in the manual?

Eaton QD5 Specifications

General IconGeneral
BrandEaton
ModelQD5
CategoryCables and connectors
LanguageEnglish

Related product manuals