Table8. Quik-start set-up for basic regulation
Function code Description Instructions
Security
099 Security FUNC, 99, ENTER, Password (Admin), ENTER
Forward settings
001 Forward Set Voltage FUNC, 1, ENTER, EDIT, Value, ENTER
002 Forward Bandwidth FUNC, 2, ENTER, EDIT, Value, ENTER
003 Forward Time Delay FUNC, 3, ENTER, EDIT, Value, ENTER
004 Forward Line Drip Comp. Resistance FUNC, 4, ENTER, EDIT, Value, ENTER
005 Forward Line Drip Comp. Reactance FUNC, 5, ENTER, EDIT, Value, ENTER
Reverse settings
056 Reverse Sensing Mode FUNC, 56, ENTER, Scroll - Locked Forward; Locked Reverse; Reverse Idle;
Bi-directional; Neutral Idle; Co-generation; React Bi-directional; Bias
Bi-directional, Bias Co-generation; Reverse Co-generation, ENTER
039 Source Voltage Calculation FUNC, 39, ENTER, EDIT, Scroll - On or Off, ENTER
140 Regulator Type FUNC, 140, ENTER, EDIT, Scroll - Type A; Type B; Type C; Type D, ENTER
044 Internal PT Ratio FUNC, 44, ENTER, Down Arrow, EDIT, Value, ENTER
146 Vin PT Configuration FUNC, 146, ENTER, EDIT, Scroll - Vdiff without RCT2; Vin Mode; Vdiff with
RCT2, ENTER
051 Reverse Set Voltage FUNC, 51, ENTER, EDIT, Value, ENTER
052 Reverse Bandwidth FUNC, 52, ENTER, EDIT, Value, ENTER
053 Reverse Time Delay FUNC, 53, ENTER, EDIT, Value, ENTER
054 Reverse Line Drip Comp. Resistance FUNC, 54, ENTER, EDIT, Value, ENTER
055 Reverse Line Drip Comp. Reactance FUNC, 55, ENTER, EDIT, Value, ENTER
Configurations
041 Regulator Configuration FUNC, 41, ENTER, EDIT, Scroll - Wye; Delta Lagging; Delta Leading,
ENTER
042 Control Operation Mode FUNC, 42, ENTER, EDIT, Scroll - Sequential; Time-Integrating; Voltage-
Averaging, ENTER
043 System Line Voltage FUNC, 43, ENTER, EDIT, Value, ENTER
044 Overall PT Ratio FUNC, 44, ENTER, EDIT, Value, ENTER
045 C.T. Primary Rating FUNC, 45, ENTER, EDIT, Value, ENTER
049 Tap-Changer Type FUNC, 49, ENTER, EDIT, Scroll - Cooper QD8; Cooper QD5; Cooper
QD3; Cooper Spring Drive; Cooper Direct Drive; Siemens;
General Electric; Howard; LTC-Reinhausen, ITB; Toshiba; User-
Defined, ENTER
050 System Calendar and Clock FUNC, 50, ENTER, EDIT, Month, Day, Year, Hour, Minute, ENTER
069 Auto Operation Blocking Status FUNC, 69, ENTER, EDIT, Scroll - Normal; Blocked, ENTER
Voltage reduction
070 Voltage Reduction Mode FUNC, 70, ENTER, EDIT, Scroll - Off; Local/Digital Remote; Remote/
Latch, Remote/Pulse, ENTER
072 Local/Digital Reduction Value FUNC, 72, ENTER, EDIT, Value, ENTER
073 Remote #1 Value FUNC, 73, ENTER, EDIT, Value, ENTER
074 Remote #2 Value FUNC, 74, ENTER, EDIT, Value, ENTER
075 Remote #3 Value FUNC, 75, ENTER, EDIT, Value, ENTER
076 # of Pulse Reduction Steps FUNC, 76, ENTER, EDIT, Value, ENTER
077 % of Voltage Red Per Pulse Step FUNC, 77, ENTER, EDIT, Value, ENTER
Voltage limiter
080 Voltage Limiter Mode FUNC, 80, ENTER, EDIT, Scroll - Off; High Limit Only; High/Low Limit;
IVVC High Limit Only; IVVC High/Low Limits, ENTER
081 High Voltage Limit FUNC, 81, ENTER, EDIT, Value, ENTER
082 Low Voltage Limit FUNC, 82, ENTER, EDIT, Value, ENTER