Assembly
ElectricalInstallation
G
eneralNotes
Electricalinstallationsandconnections
mustbeperformedbyelectrical
specialistsexclusively.Specifications
andregulationsofVDE/ÖVE/SEVand
EVUmustbecompliedwith.
15
1
Dim
ensioningofpowerconnection
wiring
Allexternalconnectionwiresmustnot
bestrippedmorethan30mm.Thehot
leadfromstrainrelieftocleatsmust
tightenupbeforethegroundedwirein
casetheyslipoutofthestrainrelief(2).
Thewirelengthmustbedimensioned
accordingly.Allwiresmustberouted
aroundthedividingplate.
2
3
Po
werconnectionandconnectionof
customer-providedwiring
Theequipmentisdesignedforafixed
connectionandforoftypeNYM
3x1.5mm
2
orH05W-F3x1mm
2
.
Condensingboilerandswitchpanel
arewired.
Thepowerconnectionismadeatthe
terminalstrip(1)oftheequipment
usingapowercircuitintendedand
fusedforthispurpose.All-pole
switcheswithacontactopeningof
>3mmorautomaticcutoutswitches
canbeused.
Linevoltage:230V,50Hz
Powerconnectionfuse:10A
Powerconsumption:max.420W
Powerconsumptionsystempump(s)
Max.switchingcurrentLMU1A/relay
Max.5Atotal
Note:
IfTRIGONLisoperatedwithamixer
circuitconnectedviaAGU2.500,a
jumpermustbeinstalledacrosslugs
50/51(X10-01).