ProductDescription
TechnicalData
TRI
GON
65
TRIGON
85
TRIGON
100
TRIGON
120
Nominalheatoutputat75°/60°CMax./Min. kW 59,1/8,4 78,1/15,6 87,8/17,6 109,9/22,0
Nominalheatoutputat40°/30°C kW 64,7/9,4 85,6/17,5 96,3/19,7 120,6/24,7
Nominalheatload kW 60,7/8,6 80,0/16,0 90,0/18,0 112,4/22,5
Standarddegreeofutilization75°/60°C % 107,3 107,5 107,5 107,5
Standarddegreeofutilization40°/30°C % 110,7 111,0 111,0 111,0
StandbylossTK=70°C % <0,2 <0,2 <0,2 <0,2
Max.pumppressureofblower Pa 230
Watervolume l 6,6 8,4 10,3 12,0
Max.permissiblewaterpressure bar 6 6 6 6
Max.permissibleflowtemperature °C 85 85 85 85
A
mountofcondensateat
4
0°/30°C ca.l/h 9,7 12,8 14,4 18,0
ConnectedgasloadNaturalgasE/H*(Hi=34,0MJ/m
3
) m
3
/h 6,4 8,5 9,5 11,9
NaturalgasLL(H
i
=
29,3MJ/m
3
)
DE,AT m
3
/
h 7,5 9,8 11,1 13,8
LiquidgasPropane(Hi=45,6MJ/kg) kg/h 4,8 6,3 7,1 8,9
Min.gasflowpressureNaturalgas
Liquidgas
mbar
mbar
20
50
20
50
20
50
20
50
Max.gaspressure mbar 60 60 60 60
Exhaustmassflowfornaturalgas g/s 31 41 46 58
ExhausttemperaturenetTV/TR75/60 °C 70 70 70 70
ExhausttemperaturenetTV/TR40/30 °C <55 <55 <55 <55
Gascategory II2ELL3P/II2H3P
Exhaustvaluecategory G61 G61 G61 G61
Exhaustsystemmodel(B23,C13,C33,C43,C53,C63,C83) all all all all
Ionizationflowmin.
mA
15,0 15,0 15,0 15,0
ConnectorsAir/Exhaustpipe(concentric) DN 110/150 110/150 110/150 110/150
Air/Exhaustpipe(parallel) DN 110/110 110/110 110/110 110/110
Heatingflow/heatingreturn DN 32 32 32 32
Gasconnector DN 20 20 20 20
Expansionvessel DN 20 20 20 20
Condensatehoseconnector mm 25 25 25 25
pHvalueofcondensate pH 3,0 3,0 3,0 3,0
Electricload/powerload230V/VAC(assisted) W 240 321 363 418
CEIdentifier 0063BQ3008
Weightapprox kg 115 120 145 150
Nominalheatoutputat80°/60°C kW 59,1 78,0 87,8 109,8
Efficiencyatnom.heatoutputat100%,80°/60°C % 97,3 97,5 97,5 97,7
Efficiencyatpartialloadat30%,40°/30°C % 109,4 109,6 109,6 109,8
Standbylossesat70°Cavg.boilertemperature % <0,2 <0,2 <0,2 <0,2
Auxiliarypowerboiler+integratedboilercircuitpump:
Standardboiler
Withlowlossheader
Withplateheatexchanger
W
W
W
193
180
180
274
274
274
332
302
302
385
355
355
7