NotesonSystemIntegration
Chimney
ExhaustVenting
CondensateLines
Con
densingBoiler
Incondensingboilers,residualheatis
extractedfromtheexhaustgases
throughcoolingandcondensation,and
subsequentlyfedbackintotheheating
system.Thisensuresahighdegreeof
efficiencyandlowenergyconsumption.
ChimneyNotes
Exhaustventsmustbeinstalledina
shaftcompliantwithDIN18160/Part1.
Priortoassemblyofanycondensing
boiler,alwayschecktheexhaust
ventsystem.
Dimensionsshallbeapplicabletothe
useofapolypropylene(PPS)exhaust
systempursuanttoDN110/150only.
Thelowexhausttemperaturesrequire
commerciallyavailableexhaustvents
applicabletocondensingboilers.
Examples:
-
Chi
mneysresistanttomoisture
-
I
nteriorshellsresistanttocondensate
-
Cer
tifiedexhaustvents
-
Dia
metersofconnectors(sleeves)
mustbetakenintoconsiderationfor
minimumshaftdiameters
Exhaustventingvia
-
ex
haustlinecertifiedandchecked
accordingtoDIBT(Germany),VKF
(Switzerland),orÖTZ(Austria)
-
ch
imney
Conduitpipesandsectionsmustbe
-
freelyaccessibleandcheckablefrom
outsidetheshafts,andmustbepro-
tectedfromfreezing;
-
r
earventilatedfrominsidetheshafts
Exhaustventsmustbe
-
r
esistanttomoisture
-
suitableforexhausttemperatures
below40°C
-
su
itableforexcessivepressure
Recommendation:
Accessoryset:Exhaustvents
Condensatepipesmustnotbe
installedinfixedposition.
Thecondensateiscollectedinafunnel
anddischargedintothesewersystem.
Recommendation:
Accessory:Neutralizingdevice
ComplywithworksheetATVA251.
DANGER:
Dangerofpoisoning!Ifthe
siphonisnotfullofwater,orwith
openconnections,fluegasesarising
canputpeopleinmortaldanger.
9
ExhaustVents
Ventilation/exhaustsystem
Applicablelocalregulationsmustbe
compliedwithwheninstallingthe
exhaustsystem.
TheTRIGOLLcompactheatingcenter
mustbeoperatedwithanapproved
exhaustsystemonly.Customer
suppliedexhaustsystemsmustbe
resistanttomoisture,corrosion,and
condensate,andmustcomplywithall
staticandoperationalrequirements.
Thefireplaceopeningmustpermitan
unencumberedexitingoftheexhaust
gases(fireplacecapisnotrecom-
mended).
Theconnectionbetweenfireplaceand
TRIGONLmustbesloped(3%)so
thattheaccumulatingcondensatemay
flowbackfromtheexhaustpipe.This
connectionshouldhaveasfewbends
aspossible.Theexhaustventshall
haveinspectionopeningspursuantto
governmentregulations.Theuseofa
roomairindependentexhaustsystem
ispossible.
Exhaustpipes
Horizontalpipelayoutmustbeavoided
inordertoavoidanysettlingofconden-
sate.Youmustensurethatthevarious
componentsareconnectedandsealed
tightly.
Anyassemblyshalluse45°bends.
Verticalpartsshallbefastenedwith
straps.
Condensate
Theconnectionofthecondensate
discharge(behindboiler)mustbe
slopedintothedischargeline.Itmust
alsobeprotectedagainstfreezing.
Installationexampleforseparate
condensatedischargefromexhaust
vent.