EasyManuals Logo
Home>EnerSys>Camera Accessories>PowerSafe

EnerSys PowerSafe User Manual

EnerSys PowerSafe
46 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #17 background imageLoading...
Page #17 background image
Page 10 www.enersys.com Publication No. US-RE-IOM-002 January 2012
4.0 BATTERY STORAGE BEFORE INSTALLATION
4.1 General
Batteries should be unpacked, installed and charged as soon as possible after receipt.
However, if this is impractical, follow the instructions below for storing the battery before
installation.
Store the battery at a dry, clean and preferably cool and frost-free location. Temperature limits
for storage are -20°C (-68 °F) to +45°C (113 °F), Humidity < 90% RH. Self discharge will occur
when a battery is left at rest (without charge) and periodic freshening charge is required. Failure
to charge batteries at the required intervals may result in irreversible damage.
Batteries that were previously in service or previously installed must be fully charged before
storing for long periods of time.
Self discharge will increase:
With natural aging of the cell
Following faulty use such as excessive over-discharge, bad maintenance, or by the
addition of non-demineralized water
Temperature rise
Do NOT stack pallets. DAMAGE MAY OCCUR AND THE WARRANTY WILL BE VOIDED.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys PowerSafe and is the answer not in the manual?

EnerSys PowerSafe Specifications

General IconGeneral
BrandEnerSys
ModelPowerSafe
CategoryCamera Accessories
LanguageEnglish

Related product manuals