A W-TRAC
IOM‐49 12of12 Mar99R4
Slowlyrotatepot#2counterclockwise(EXCAL))untilthelowexhausttemperaturelightcomeson.
Slowlyrotatepot#2clockwiseuntilthelowexhausttemperaturelightjustturnsoff.
ReconnectallsensorsandsetpotBDRHbacktoitsoriginalposition.

Humiditysensors
AccuratelymeasuretherelativehumidityatthesensorlocationandcomparetothesensorVdcoutput.
The0‐10Vdcoutputisproportionalto0‐100%RH.
SENSORTABLE
SensorResistanceChartforTE6000EA3
Table2
°C °F
Resistance
°C °F
Resistance
°C °F
Resistance
‐40 ‐40 602 18.3 65 983 48.9 120 1234
‐34.4 ‐30 633 20 68 996 54.4 130 1269
‐28.9 ‐20 665 20.6 69 1000.7 60 140 1333
‐23.3 ‐10 698 21.1 70 1005 65.5 150 1365
‐17.8 0 732 23.9 75 1026.5 71.1 160 1437
‐12.2 10 768 26.7 80 1048 76.7 170 1491
‐8.7 20 804 29.4 85 1070 82.2 180 1546
‐1.1 30 842 32.2 90 1092 87.7 190 1602
4.4 40 881 35.6 95 1116 93.3 200 1659
10 50 921 37.8 100 1139 98.8 210 1718
12.8 55 942 43.3 110 1186 100 212 1778
Referenceresistanceis1035ohmsat77°F.Resistancetolerancesare±0.05to0.15%at77°F.Temperature
range+32to+104°F.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Engineered air EngA W-TRAC and is the answer not in the manual?

Engineered air EngA W-TRAC Specifications

General IconGeneral
BrandEngineered air
ModelEngA W-TRAC
CategoryController
LanguageEnglish

Related product manuals