A W-TRAC
IOM‐49 9of12 Mar99R4
Whentheoutdoorambienttemperatureisbelow15°F(‐10°C)thespeedoftheheatwheelwillbereduced
tomaintaintheleavingexhaustairhumiditybetween80–90%.Thisapplicationrequireshighaccuracy
humiditysensors.
RETURNAIRRH%SENSOR
ThismethodoffrostcontrolrequiresaRHsensorinstalledintheequipmentreturnairsection,justbefore
theheatwheel,wiredintoterminalsRMHandC2.DIP3mustbeON,DIP1and2mustbeOFF.
UsingthevaluesoftheRHandambient(outsideair)sensor,theW‐TRACcalculatestheminimum
allowableexhaustairtemperaturethatwillkeepfrostfromformingonthewheel.
BDRHPREDICTEDRETURNAIRRELATIVEHU MIDITY
RH%sensingisnotusedinthismethodoffrostcontrol.DIP1and3mustbeON,whileDIP2isOFF.
TheW‐TRACmayoperatewithouttheuseofhumiditysensinginsituationswheretheRH%valuesare
expectedtobereasonablyconstant.Inthesecases,theW‐TRACoperatesbysensibletemperatureonly.
Whenenabled,theBDRHpot(BuildingDesignRelativeHumidity)issetaccordingtotheexpecteddesign
returnairconditions.RefertothetablebelowtosettheexpectedvaluesbasedontemperatureandRH%.
Table1
BDRHsetting
ReturnAirConditions
70°F(21°C) 75°F(24°C) 80°F(27°C)
1 <25% <21% <18%
2 26–32% 22–27% 19–23%
3 33–39% 28–33% 24–27%
4 40–49% 34–42% 28–35%
Tousethistable,firstselectthereturnairtemperature,thenselecttheRH%rangeinthecolumnbelow,
thenselecttheBDRHsettingtotheleft.
WIRING
TheW‐TRACterminalsHandNrequireaminimum24VAC,40VAclass2powersupplythatdoesnotneed
tobeisolatedfromtherestofthesystemscomponents.
TerminalNshouldbewiredtothecommonofthesamesourcesupplyingpowertoterminalsE,A,andK.
Allremotewiringshouldbeinstalledinaclean(noelectricalnoise)environment.Wiresizeshouldbea
minimumof24ga.twistedpairtoreduceelectricalnoise(shieldedwireisrecommended).Forlongerruns