A W-TRAC
IOM‐49 5of12 Mar99R4
INTRODUCTION
TheW‐TRACisasupervisorycontrollerforEngineeredAirHRWheatwheels,withbuiltindischargeair
temperaturecontrolandoptionalexhaustfrostcontrol.
Theinformationusedinthismanualshouldbeusedinconjunctionwiththeunitfunctionsheet(s)andthe
HRWseriesInstallation,Operation,andMaintenancemanual.
TheW‐TRACisdesignedtocontrolonlyEngineeredAirequipment.Variousupgradesandimprovements
havebeenmadeovertime.Alwaysincludeanysuffixlettersandnumbersfortroubleshootingand/or
replacement.AllW‐TRACmodelsarebackwardscompatible;howeversomeadditionalwiringmaybe
required.
Note:Itisnecessarythatalloftheremotewiringandcontrolsbecompleteandoperationalbeforestarting
theappliance.
CONTROLLERRATINGS
Powerrequirements:24VAC,40VA.
ContactRating:120V3Ainductive
0‐10Vdcinputimpedance:5k
Environment:‐40to120°F(‐40to50°C)non‐condensing.