Primary meter
Records the system's load curve and provides measurement data for
energy profiling in Fronius Solar.web. The primary meter also controls
the dynamic feed-in control.
Secondary meter
Records the load curve of individual loads (e.g. washing machine,
lamps, TV, heat pump, etc.) in the consumption branch and provides
measurement data for energy profiling in Fronius Solar.web.
Producer meter
Records the load curve of individual producers (e.g. wind power plant) in
the consumption branch and provides measurement data for energy pro-
filing in Fronius Solar.web.
Loads in the system
e. g. washing machine, lamps, TV, etc.
Additional loads in the system
e. g. heat pump
Additional producers in the system
e. g. wind power plant
Terminating resistor
R 120 Ohm
Multi-meter sys-
tem
If several Fronius Smart Meter TS are installed, a separate address must be set for each
(see Setting the address on the Fronius Smart Meter TS on page 27). The primary
meter is always assigned address 1. All the other meters are numbered consecutively
with the address range from 2 to 14. Different Fronius Smart Meter power categories can
be used in combination.
IMPORTANT!
Max. Use 3 secondary meters in the system.
25
EN

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fronius Smart Meter TS Series and is the answer not in the manual?

Fronius Smart Meter TS Series Specifications

General IconGeneral
BrandFronius
ModelSmart Meter TS Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals