8
Installation posi-
tion of the invert-
er
The inverter is designed to be dustproof in principle. However, in areas
of high dust accumulation, the cooling surfaces can become dusty, which
can impair the thermal performance. In this case, the dust must be re-
moved regularly. We therefore recommend that installation is not carried
out in areas and environments with high dust accumulation (e.g., iron fil-
ings) as this can cause damage to the inverter.
Do not install the inverter in:
- greenhouses
- storage or processing areas for fruit, vegetables, or viniculture prod-
ucts
- areas used in the preparation of grain, green fodder, or animal
feeds.
The inverter is suitable for vertical installation on a vertical wall or column.
The inverter is suitable for a horizontal installation position.
The inverter is suitable for installation on a sloping surface.
Do not install the inverter on a sloping surface with the connections up-
wards.
Do not install the inverter in a sloping position on a vertical wall or col-
umn.
Do not install the inverter in a horizontal position on a vertical wall or col-
umn.