11-8
11.4.2 Compliance with the harmonic component regulation
Table 11.3 Compliance with Harmonic Component Regulation
Power supply
voltage
Inverter type w/o DC reactor w/ DC reactor
Applicable
DC reactor type
FRN0.1C1
-2
* * DCR2-0.2
FRN0.2C1
-2
* * DCR2-0.2
FRN0.4C1
-2
* * DCR2-0.4
Three-phase
200 V
FRN0.75C1
-2
* * DCR2-0.75
FRN0.4C1
-4
DCR4-0.4
Three-phase
400 V
FRN0.75C1
-4
DCR4-0.75
FRN0.1C1
-7
DCR2-0.2
FRN0.2C1
-7
DCR2-0.4
FRN0.4C1
-7
DCR2-0.75
Single-phase
200 V
FRN0.75C1
-7
DCR2-1.5
* Inverter types marked with in the table above are compliant with the EN61000-3-2 (+A14), so they may
be connected to public low-voltage power supply unconditionally.
Conditions apply when connecting models marked with “—“. If you want to connect them to public low-
voltage power supply, you need to obtain permission from the local electric power supplier. In general,
you will need to provide the supplier with the harmonics current data of the inverter. To obtain the data,
contact your Fuji Electric representative.
Note 1) A box (
) in the above table replaces S or E depending on the enclosure.
A box (
) in the above table replaces A, C, E, or J depending on the shipping destination.
2) When supplying three-phase 200 VAC power stepped down from a three-phase 400 VAC power
line using a transformer, the level of harmonic flow from the 400 VAC line will be regulated.
11.5 Compliance with the Low Voltage Directive in the EU
11.5.1 General
General-purpose inverters are regulated by the Low Voltage Directive in the EU. Fuji Electric has
obtained the proper certification for the Low Voltage Directive from the official inspection agency.
Fuji Electric states that all our inverters with CE and/or TÜV marking are compliant with the Low
Voltage Directive.
11.5.2 Points for consideration when using the FRENIC-Mini series in a system to be
certified by the Low Voltage Directive in the EU
If you want to use the FRENIC-Mini series of inverters in systems/equipment in the EU, refer to the
guidelines on page vii.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fuji Electric FRN0.75C1*-2 Series and is the answer not in the manual?

Fuji Electric FRN0.75C1*-2 Series Specifications

General IconGeneral
BrandFuji Electric
ModelFRN0.75C1*-2 Series
CategoryInverter
LanguageEnglish

Related product manuals