8-3. Current release control
The compressor frequency is controlled so that the outdoor unit input current does not exceeds cur-
rent limit value set according to the outdoor temperature.
The compressor frequency returns according to the operation mode, when the current becomes low-
er than the release value.
¢ Model: AOYG36KRTA
Operation mode Outdoor temp. (Ta) Trigger condition Release condition
Cooling
52°C ≤ Ta 3.5 A 3.0 A
50°C ≤ Ta < 52°C 5.5 A 5.0 A
42°C ≤ Ta < 50°C 6.0 A 5.5 A
2°C ≤ Ta < 42°C 7.5 A 7.0 A
Ta < 2°C 8.5 A 8.0 A
Heating
20°C ≤ Ta 5.5 A 5.0 A
16°C ≤ Ta < 20°C 6.0 A 5.5 A
12°C ≤ Ta < 16°C 7.0 A 6.5 A
2°C ≤ Ta < 12°C 7.5 A 7.0 A
Ta < 2°C 8.5 A 8.0 A
¢ Model: AOYG45KRTA
Operation mode Outdoor temp. (Ta) Trigger condition Release condition
Cooling
52°C ≤ Ta 4.5 A 4.0 A
50°C ≤ Ta < 52°C 5.5 A 5.0 A
46°C ≤ Ta < 50°C 6.5 A 6.0 A
42°C ≤ Ta < 46°C 7.5 A 7.0 A
2°C ≤ Ta < 42°C 8.5 A 8.0 A
Ta < 2°C 10.0 A 9.5 A
Heating
20°C ≤ Ta 6.5 A 6.0 A
16°C ≤ Ta < 20°C 7.0 A 6.5 A
12°C ≤ Ta < 16°C 8.0 A 7.5 A
2°C ≤ Ta < 12°C 8.5 A 8.0 A
Ta < 2°C 10.0 A 9.5 A
8-4. Indoor unit fan motor over temperature protection
When satisfy the following conditions, the protection works.
After the 90 seconds from the fan operation, detect less than 300 rpm for 10 seconds.
IPM trip protection works.
Current overload protection works.
When detecting the above condtion, recheck the condition after 6 minutes. When count the twice,
the protection works.
Protection contents
Reduce the static pressure 20 Pa. When it does not dissolve even the minimum static pressure
condition, work the following operation.
Fan motor error displayed when less than 300 rpm for 10 seconds is detected after the 90 sec-
onds from the fan operation.
Fan stop 40 seconds when IPM trip protection works.
Fan stop 50 seconds when corrent overload protection works.
8-3. Current release control
- (04-29) - 8. Various protections
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ABYG36KRTA and is the answer not in the manual?

Fujitsu ABYG36KRTA Specifications

General IconGeneral
StyleSplit-type
ColorWhite
FeaturesBladeless Design
Min/Max: 0.50-3.20 kW000 BTU/h
Min/Max Cooling 2.20/8.00 kW?860-11
29.5 (2.8 - 11.2) kW
Min/Max: 0.50-4.40 kW000 BTU/h
Min/Max Heating 1.90/9.00 kW?000 Btu/h
Moisture Removal2.60 l/h
Fan Airflow RateHigh / Mid / Low: [CMM] (C) 17.5/15.9/14.3 (H) 17.5/15.9/14.3 CMM
Heating (?): 10.0 ~ 45.0 ?Cooling: -15 to 46 °C DB
Sound Pressure LevelIndoor (Cooling) : High 44 dB(A)
Indoor (Heating): High 44 dB(A)36 / 26 / 23 dBA (H / L / QLo)
Refrigerant TypeR32
Refrigerant Charge-
Annual Energy ConsumptionCooling: 524 kWh/a
Heating: 2904 kWh/a-
Heating: 4.12 WCooling: 2.910 kW
Frequency50 Hz
Voltage230 V
Heating: 6.60 AMax Cooling: 22.60 A
Battery Life-
Battery Capacity-
Depth705 mm
Height235 mm
Width1700 mm
Net Weight38.0 kg