2-4. E: 15. Automatic air flow adjustment error (Indoor unit)
Indicator
Wired remote
controller
Error code E: 15
Detective actuator Indoor unit Main PCB
On automatic airflow adjustment operation, when
the fan speed other than 0rpm is detected at the
0rpm operation.
On automatic airflow adjustment operation, when
the fan speed is not reach the target speed, after 2
minutes from the fan started.
On automatic airflow adjustment operation
operation, when the 72:750W,90:1000W of input
power is detected.
Forecast of cause
Fan rotation failure
Fan motor winding open
Indoor unit main PCB
Check point 1. Check the rotation of fan
Rotate the fan by hand when the operation is off. (Check if fan is caught, drop off or locked motor)
→ If fan or bearing is abnormal, replace it.
Check point 2. Check ambient temperature around the motor
Check excessively high temperature around the motor. (If there is any surrounding equipment that
causes heat.)
→ Upon the temperature coming down, restart operation.
Check point 3. Check indoor unit fan motor
Check indoor unit fan motor. (Refer to indoor unit fan motor in "Error code table (Outdoor unit)" on
page 03-2.)
→ If indoor unit fan motor is abnormal, replace it.
Check point 4. Replace main PCB
If check point 1-3 does not improve the symptom, change main PCB.
End
2-4. E: 15. Automatic air flow adjustment error (Indoor unit) - (03-9) - 2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ABYG36KRTA and is the answer not in the manual?

Fujitsu ABYG36KRTA Specifications

General IconGeneral
StyleSplit-type
ColorWhite
FeaturesBladeless Design
Min/Max: 0.50-3.20 kW000 BTU/h
Min/Max Cooling 2.20/8.00 kW?860-11
29.5 (2.8 - 11.2) kW
Min/Max: 0.50-4.40 kW000 BTU/h
Min/Max Heating 1.90/9.00 kW?000 Btu/h
Moisture Removal2.60 l/h
Fan Airflow RateHigh / Mid / Low: [CMM] (C) 17.5/15.9/14.3 (H) 17.5/15.9/14.3 CMM
Heating (?): 10.0 ~ 45.0 ?Cooling: -15 to 46 °C DB
Sound Pressure LevelIndoor (Cooling) : High 44 dB(A)
Indoor (Heating): High 44 dB(A)36 / 26 / 23 dBA (H / L / QLo)
Refrigerant TypeR32
Refrigerant Charge-
Annual Energy ConsumptionCooling: 524 kWh/a
Heating: 2904 kWh/a-
Heating: 4.12 WCooling: 2.910 kW
Frequency50 Hz
Voltage230 V
Heating: 6.60 AMax Cooling: 22.60 A
Battery Life-
Battery Capacity-
Depth705 mm
Height235 mm
Width1700 mm
Net Weight38.0 kg