Check Point : ARUH36TLAV (High Static Pressure Duct Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Red Violet
Violet Blue
Red Black
White Red
Lead wire
19.8
7%
23.4 7%
8.75 7%
8.75 7%
Resistance value
(AC)
Thermal protector
Pr
VIOLET (Med)
BLUE (Low)
RED (Hi)
BLACK
WHITE
150°C
at 20°C
Check Point : ARUH48/ 60TLAV (High Static Pressure Duct Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Red Violet
Violet Blue
Red Black
White Red
Lead wire
8.94
7%
9.56 7%
3.41 7%
2.65 7%
Resistance value
(AC)
Thermal protector
Pr
VIOLET (Med)
BLUE (Low)
RED (Hi)
BLACK
WHITE
145°C
at 20°C
04-114
SERVICE PARTS INFORMATION 20
Indoor Unit AC Fan Motor