1-8 Field Setting / Function Setting for Outdoor air unit
Indoor unit field setting
setting by
remote controller
Setting Mode
ITEM
CODE No.
ITEM
CODE No.
Setting Function DefaultClassification
00
Address Indoor unit address 00~63 00~63
02 Refrigerant circuit address 00~99 00~99
Filter 11 Filter indicator Interval
00 Default
01
Longer
02
Shorter
13 Filter sign display
00 Enable
01
Disable
02 Display only on central remote control
Airflow
26
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
31
SP mode 05
[ 0.20 in.WG ( 50 Pa) ]
SP mode 06 [ 0.24 in.WG ( 60 Pa) ]
SP mode 07 [ 0.28 in.WG ( 70 Pa) ]
SP mode 08 [ 0.32 in.WG ( 80 Pa) ]
SP mode 09 [ 0.36 in.WG ( 90 Pa) ]
SP mode 10 [ 0.40 in.WG ( 100 Pa) ]
SP mode 11 [ 0.44 in.WG ( 110 Pa) ]
SP mode 12 [ 0.48 in.WG ( 120 Pa) ]
SP mode 13 [ 0.52 in.WG ( 130 Pa) ]
SP mode 14 [ 0.56 in.WG ( 140 Pa) ]
SP mode 15 [ 0.60 in.WG ( 150 Pa) ]
SP mode 16 [ 0.64 in.WG ( 160 Pa) ]
SP mode 17 [ 0.68 in.WG ( 170 Pa) ]
SP mode 18 [ 0.72 in.WG ( 180 Pa) ]
SP mode 19 [ 0.76 in.WG ( 190 Pa) ]
SP mode 20 [ 0.80 in.WG ( 200 Pa) ]
SP mode 21 [ 0.84 in.WG ( 210 Pa) ]
SP mode 22 [ 0.88 in.WG ( 220 Pa) ]
Normal SP
Static Pressure setting
- Outdoor air unit Only -
The Range of static pressure is
different from one model to other.
40 Auto restart *1 00 Enable
01 Disable
43 Cool air prevention 00 Super low
01 Follow the setting on the remote controller
46 External control 00 Start / Stop
01 Emergency stop
47
Error report target
00
01
00
All
01 Display only for central remote control
02 Forced stop (Start/Stop by RC is restricted)
60,61,62
Forbidden
63
Humidifier control *2
65 Threshold temperature setting
for cool / heat switch over*3
00
01
02
00
01
02
03
04
05
mode 00
mode 01
mode 02
mode 1 +
4
°
F (+2
°C)
mode 0 +
10
°
F (+5
°C)
mode 2 +
6
°
F (+3
°C)
mode 3 +
8
°
F (+4
°C)
mode 4 +
10
°
F (+5
°C)
mode 5 +
12
°
F (+6
°C)
06
mode 5 +
14
°
F (+7
°C)
-
-
-
-
-
-
-
-
-
-
-
-
-
*1: Auto restart is an emergency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation.
Be sure to operate by the control unit, converter or external input device.
*2: Select control conditions of external output.
Threshold temperature setting for cool / heat mode under auto operation ; Set temperature +
4
°
F (+2
°C) to +
14
°
F (+7
°C)
*Cool / heat mode tends to be switched as the threshold temperature range gets smaller,
and cool / heat mode becomes difficult to be switched as the threshold temperature range gets larger.
Set the proper value according to use conditions.
"Mode 00" is output when heating thermostat is ON, "Mode 01" is output in heating operation, "Mode 02" is output in heating operation and in fan operation.
*3:
-- - -
Change of
function 2
Change of
function 1
00
00
Model name
AAUA48TLAV
AAUA72TLAV
AAUA96TLAV
Range of static
pressure
SP mode 05 to 19
(0.2 to 0.76 in.WG)
SP mode 05 to 20
(0.2 to 0.80 in.WG)
SP mode 05 to 22
(0.2 to 0.88 in.WG)
Normal static
pressure
0.74 in.WG
(185 Pa)
0.80 in.WG
(200 Pa)
0.80 in.WG
(200 Pa)
01-27