6. SYSTEM DESIGN
Example 9 (Prohibited)
Outdoor unit
Indoor unit 1
Branch box 1
(3 branches type)
Indoor unit 2 Indoor unit 3
Model
Rated
capacity
of cooling
(kW)
Total
capacity
(kW)
Connectable indoor
unit capacity (kW)
Judgement
Min. Max.
Outdoor unit AO45 14.0 14.0
80%
11.2
130%
18.2
Prohibited  ecause  is
included in this combination.
Indoor unit 1 AS12LM 3.52
11.72
Indoor unit 2 AS14LU 4.10
Indoor unit 3 AS14LM 4.10
Branch box 1
UTP-PY03A
-
-
- -
-
* Combination prohibited when including at least one AS14LM (Model code) : 12 + 14 + 14
14 + 14 + 14
- (06 - 07) -