Data subject to change without notice 7/07. © 2007 GE Drives
11. Specifications
Three-phase 230V series
F25 F50 001 002 003 005 007 010 015 020 025 030 040 050 060 075 100 125
Nominal 230V system pplied motor HP 1/4 1/2 12357.5101520253040506075100125
Output Rated Capacity *1) kVA 0.59 1.1 1.9 3.1 4.3 6.7 9.9 13 18 23 29 34 45 57 71 85 112 137
ratings Rated Voltage *2) V 3-phase, 200V /50Hz , 200V ,220V ,230V /60Hz
Rated Current *3) A 1.5 3.0 5.0 8.0 11 17 25 33 46 59 74 87 115 145 180 215 283 346
Overload Capability 150% of rated current for 1min , 200% of rated current for 0.5s 150% of rated current for 1min ,
3-phase, 200 to 230V , 50/60Hz 3-phase, 200 to 220V /50Hz , 200 to 230V /60Hz
ratings * 220 to 230V /50Hz *4),
Voltage / frequency variations -Voltage : +10 to -15% ( Voltage unbalance *5) : 2% or less ) -Frequency :+5 to -5%
Momentary voltage dip When the input voltage is 165V or more, the inverter can be operated continuously.
capability *6) When the input voltage drops below 165V from rated voltage, the inverter can be operated for 15ms . (within
85% load of nominal applied motors)
The smooth recovery method is selectable.
Output Maximum Freq. 50 to 400Hz *11)
frequency Base Freq. 25 to 400Hz *11)
Starting Freq. 0.1 to 60Hz , Continuous time : 0.0 to 10.0s
Carrier Freq. *8) 0.75 to 15kHz The minimum carrier frequency changes depend on maximum output frequency. 0.75 to 10kHz
Accuracy (Stability)
-Analog setting : ±0.2% of Maximum frequency (at 25 ±10 degrees C)
-Digital setting : ±0.01% of Maximum frequency (at -10 to +50 degrees C)
Setting resolution
-Analog setting : 1/3000 of Maximum frequency ex.) 0.02Hz at 60Hz ,0.15Hz at 400Hz
-Digital setting : 0.01Hz at Maximum frequency of up to 99.99Hz (0.1Hz at Maximum frequency of 100Hz and above)
-Link setting : Two methods are selectable.
Control Volt/Freq Characteristic 80 to 240V (with AVR control) at base and maximum frequency, adjustable
Torque boost Constant toruque load Variable torque load
Automatic (setting code) :0.0 -
Manual (setting code) :2.0 to 20.0 0.1 to 1.9 *9)
Starting torque 200% (with Dynamic torque vector control selected) 180% (with Dynamic torque vector control selected)
Braking Braking torque 150% 100% 20% *10) 15 to 10% *10)
Standard Time s 10 5 5 No limit
Duty cycle % 10 5 3 5 3 2 3 2 No limit
Braking torque 150% 100%
Options Time s 90 45 45 45 30 20 10 8 10
Duty cycle % 37 22 18 10 7 5 5 5 10
DC injection braking Starting frequency : 0.1 to 60.0Hz , Braking time : 0.0 to 30.0s , Braking level : 0 to 100% of rated current
Enclosure NEMA Type1, Type4 NEMA Type1, Type12 Open, Open with NEMA Type 12 Heatsink, NEMA 1
Cooling method Natural Fan cooling
Standards -UL/cUL
NOTES
*1) Inverter output capacity [kVA] at 230V.
*2) Output voltage is proportional to the power supply voltage and can't exceed the power supply voltage.
*3) Current derating may be required in case of low impedance load such as high frequency motor.
*4) 220 to 230V/50Hz : Order individually
*5) Reference to the IEC 61800-3( 5.2.3 )
(Maximum voltage[V] - Minimum voltage[V] )
3-phase averaging voltage[V]
*6) Input power : 85%
*8) If carrier frequency is set at more than 10kHz and an overheat condition (detected by internal thermal sensor ) occurs,in
verter will automatically reduce carrier frequency to 8kHz ,
in order to avoid trip.(Available up to 30HP unit)
*9) When setting into 0.1,the starting torque gets 50%
*10) With a nominal applied motor.(Average torque when the motor decelerates and stops from 60Hz. It may change according to th
e motor loss.)
*11) Above 120Hz application, please contact the factory.