5-7
F00 Data protection
F00DATA PRTC
Setting range 0 : data can be changed
1 : data cannot be changed
This function protects the system by blocking any data
changes from the keypad panel.
Setting procedure:
0 to 1: Press the
STOP
and keys simultaneously to
change the value from 0 to 1, then press
the
FUNC
DATA
to validate the change.
1 to 0: Press the
STOP
and keys simultaneously
to change the value from 1 to 0, then press
the
FUNC
DATA
key to validate the change.
F01 Frequency setting 1
F01FREQ CMD 1
This function determines the method to be used for setting
frequency.
NOTE: Use only one terminal - V2 or C1, exclusively.
0: Keypad operation (
or key)
1: Voltage input (terminal 12 and V2) (0 to +10 VDC,
0 to +5VDC)
2: Current input (terminal C1) (4 to 20 mA DC)
3: Voltage and current input (terminals 12 and C1)
4: Reversible operation with polarity (terminal 12)
(0 to ± 10 VDC)
5: Reversible operation with polarity (terminal 12 and V1
option) (0 to ± 10 VDC)
Related functions E01 to E09 (Set values 21)
6: Inverse mode operation (terminal 12 and V2)
(+10 to 0 VDC)
7: Inverse mode operation ( terminal C1)(20 to 4 mA DC)
8: UP/DOWN control 1 (initial freq. = 0 Hz
9: UP/DOWN control 2 (initial freq. = last value)
Related functions E01 to E09 (Set values 17, 18)
10. PATTERN operation
Related functions: C21 to C28
11: DI option or Pulse train input
For details, see instruction manual on options.
F02 Operation method
F02OPR METHOD
This function determines the input method for operation
commands.
0: Keypad operation (
FWD
or
REV
or
STOP
key)
1: Terminal operation (
STOP
key active)
2: Terminal operation (
STOP
key inactive)
3: Terminal operation (
STOP
key active) with GE start
software
4: Terminal operation (
STOP
key inactive) with GE start
software
Note: GE start software prevents drive from restarting
when power is applied.
This function can only be changed when terminals
FWD
and
REV
are open.
REMOTE/LOCAL switching from the keypad panel
automatically changes the set value from 0 to 3 of this
function.
5.3 Function Explanation
F: Fundamental Functions

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE AF-300 P11 and is the answer not in the manual?

GE AF-300 P11 Specifications

General IconGeneral
BrandGE
ModelAF-300 P11
CategoryController
LanguageEnglish

Related product manuals