5-18
E: Extension Terminal Functions
E01 Terminal X1
E09 Terminal X9
E01X1 FUNC
E02X2 FUNC
E03X3 FUNC
E04X4 FUNC
E05X5 FUNC
E06X6 FUNC
E07X7 FUNC
E08X8 FUNC
E09X9 FUNC
Functions can be individually set from each of the digital
input terminals X1 to X9.
Value
Function
0,1,2,3
Multi-step frequency selection (1 to 15 steps)
4,5
Acceleration and deceleration time selection (3 steps)
6
Self-hold selection (HLD)
7
Coast-to-stop command (BX)
8
Alarm reset (RST)
9
External alarm (THR)
10
Jogging (JOG)
11
Frequency setting 2 / Frequency setting 1 (Hz 2 / Hz1)
12
Motor 2 / Motor 1 (M2 / M1)
13
DC injection brake command (DCBRK)
14
Torque limit 2 / Torque limit 1 (TL2 / TL1)
15
Switching operation from line to drive (50 Hz) (SW50)
16
Switching operation from line to drive (60 Hz) (SW60)
17
UP command (UP)
18
DOWN command (DOWN)
19
Edit permission command (WE-KP)
20
PID control cancellation (Hz / PID)
21
Normal/Inverse switching (Terminals 12 and C1) (IVS)
22
Interlock (52-2) (IL)
23
Torque control cancellation (Hz/TRQ)
24
Link communication selection (LE)
25
Universal DI (U-DI)
26
Pick up start mode (STM)
30
Timed alarm stop command (STOP1)
31
Timed alarm stop command with
Deceleration time 4 (STOP2)
Note: Values which are not set in the functions from E01
to E09 are assumed to be inactive.
Multi-step frequency selection
Value 0,1, 2, 3: The frequency can be switched to a
preset frequency in function codes C05 to C19 by
switching the external digital input signal. Assign values
0 to 3 to the target digital input terminal. The combina-
tion of input signals determines the frequency.
3210
(SS8) (SS4) (SS2) (SS1)
off off off on C05 MULTI Hz-1
off off on off C06 MULTI Hz-2 Related
off off on on C07 MULTI Hz-3 Functions:
off on off off C08 MULTI Hz-4 C05-C19
off on off on C09 MULTI Hz-5
off on on off C10 MULTI Hz-6 Setting
off on on on C11 MULTI Hz-7 Setting
on off off off C12 MULTI Hz-8 0.00 to
on off off on C13 MULTI Hz-9 - 120.00 Hz
on off on off C14 MULTI Hz-10
on off on on C15 MULTI Hz-11
on on off off C16 MULTI Hz-12
on on off on C17 MULTI Hz-13
on on on off C18 MULTI Hz-14
on on on on C19 MULTI Hz-15
Combination of
Input Signals Selected Frequency
Acceleration and Deceleration time selection
Value 4, 5: The acceleration and deceleration time can
be switched to a preset time in function codes E10 to
E15 by switching the external digital input signal. Assign
values 4 and 5 to the target digital input terminal. The
combination of input signals determines the acceleration
and deceleration times.
54
(RT2) (RT1)
off off F07 ACC TIME1
F08 DEC TIME1 Related
off on E10 ACC TIME2 Functions
E11 DEC TIME2 E10-E15
on off E12 ACC TIME3 Setting Range
E13 DEC TIME3 0.01 to 3600s
on on E14 ACC TIME4
E15 DEC TIME4
Combination
of Input Signals
Selected Acceleration /
Deceleration Times

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE AF-300 P11 and is the answer not in the manual?

GE AF-300 P11 Specifications

General IconGeneral
BrandGE
ModelAF-300 P11
CategoryController
LanguageEnglish

Related product manuals