Page #111 background imageLoading...
Page #111 background image
8-15
The motor
will not run
( 11 ) Motor will not run.
When there is no
abnormal condition
continue operation.
Will the motor run if
KEYPAD run key is
pressed?
Check the display
contents and press
the reset switch
after the failure is
corrected.
Is the wiring
between Terminals
13, 12, 11, V1, and
C1 connected
correctly?
Has the input line
circuit breaker or
contactor been
turned "ON"?
Is the voltage of the
power terminal L1,
L2, L3 correct?
Is the "CHARGE"
Lamp on?
Is the keypad
panel indicating
a protection
function operation
display?
Has forward or
reverse
command signal
been applied?
Local or remote
operation?
Has the frequency
set signal (0 to ±
10V,4 to 20mA)
been input?
Is the wiring to the
motor connected
properly?
Has the torque
boost value been
correctly set?
Will the motor run if
KEYPAD UP is
pressed?
Turn the input line
circuit breaker or
contactor to "ON".
Check for the
presence of low
voltage, missing
phase, improper
connection, failure
input line circuit
breaker or AC line
contactors.
No
Is the wiring
between FWD, or
REV-CM terminals
connected
correctly?
Poor contact in
switch or relay.
Has the motor
been locked?
Release the
lock.
No
No
Set the frequency
by pressing UP
key or DOWN key.
No
Do the drive output
terminals (U, V, W)
have applied
voltage?
Yes
Yes
Yes
Yes
Yes
Yes
Is high limiter or
frequency set
signal below the
starting frequency?
The drive is
thought to have
failed. Contact
GE Fuji.
Failure in
electric motor.
Is the load too
large?
Motor will not run under these conditions:
1. BX coast to stop command on. REV on when REV phase sequence lock is Active.
2. Wrong setting at one of F87, 88, 89, 91, or 92. When FC 07 torque boost setting is 00 or F29 torque vector control is active while using the wrong
capacity motor (FC86, 91, 92)
Increase or de-
crease the torque
boost value.
Decrease the load
or increase the
drive capacity.
Replace the fre-
quency reference
voltage or current
source and check
for ground in
reference circuit.
Yes
Yes
No
RemoteLocal
Yes
Yes
Yes
Yes
Yes
No
Yes
No
No
No
No
No
No
No
No
No
Yes
No
Yes
No
Yes
No
Yes
Set the correct
frequency.
Correct wiring.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Fuji Electric AF-300ES and is the answer not in the manual?

GE Fuji Electric AF-300ES Specifications

General IconGeneral
BrandGE
ModelFuji Electric AF-300ES
CategoryDC Drives
LanguageEnglish

Related product manuals