EasyManuals Logo
Home>GE>DC Drives>Fuji Electric AF-300ES

GE Fuji Electric AF-300ES User Manual

GE Fuji Electric AF-300ES
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #91 background imageLoading...
Page #91 background image
L CD
GRAPHIC FACTORY
FUNCTION DISPLAY SETTING DESCRIPTION SETTING
6-33
* 85 RESET INT RESET INTERVAL 5
Time interval between reset attempts as set
in Function Code 84.
2 TO 20
Time in seconds.
MOTOR CHARACTERISTICS
86 MOTOR CAP MOTOR Hp CAPACITY 1
This Function Code is used to select the
motor Hp capacity in relation to the
drive Hp capacity.
0:
One frame up in Hp capacity (variable torque
application).
1:
Standard capacity (constant torque application).
2:
One frame down in Hp capacity.
3:
Two frames down in Hp capacity.
87 MOTOR 1-Ir 0.00 TO
MOTOR #1 NAMEPLATE FULL LOAD CURRENT RATED
2000 AMPS
88 MOTOR 1-Io 0.00 TO MOTOR #1 NO LOAD CURRENT (Magnitizing
2000
current).
89 MOTOR 2-Ir 0.00 TO
MOTOR #2 NAMEPLATE FULL LOAD CURRENT RATED
2000 AMPS
90 TUNING MOTOR TUNING 0
This Function Code is used to tune the
primary resistance and inductance of the
motor.
0:
Inactive
1:
Active
WARNING: Ensure the motor is connected, free to rotate and at a standstill. Upon setting
Function Code 90 equal to 1, the drive will pulse the motor three (3) times in order to calculate
the settings in Function Codes 91 and 92.
CAUTION: When using motor tuning, be sure the correct values are set in Function Code 03, 04 and 87.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Fuji Electric AF-300ES and is the answer not in the manual?

GE Fuji Electric AF-300ES Specifications

General IconGeneral
BrandGE
ModelFuji Electric AF-300ES
CategoryDC Drives
LanguageEnglish

Related product manuals