EQUIVALENT NUMBER EQUIVALENT
DUCT PIECES LENGTH x USED = LENGTH
Rectangular-to-Round 5 Ft. x ( ) = Ft.
Transition Adaptor*
Wall Cap 40 Ft. x ( ) = Ft.
90° Elbow 10 Ft. x ( ) = Ft.
45° Elbow 5 Ft. x ( ) = Ft.
90° Elbow 25 Ft. x ( ) = Ft.
45° Elbow 5 Ft. x ( ) = Ft.
Roof Cap 24 Ft. x ( ) = Ft.
Straight Duct 6s Round or 1 Ft. x ( ) = Ft.
3
1
ø4s x 10s Rectangular
7RWDO'XFWZRUN )W
Equivalent lengths of duct pieces are based on actual tests and
reflect requirements for good venting performance with any vent
hood.
6
* IMPORTANT: If a rectangular-to-round transition
adaptor is used, the bottom corners of the damper
will have to be cut to fit, using the tin snips, in order
to allow free movement of the damper
.
NOTE: If you need to install ducts, note that the total duct
length of 3
1
ø4s x 10s rectangular or 6s diameter round duct
VKRXOGQRWH[FHHGHTXLYDOHQWIHHW
Outside ventilation requires a HOOD EXHAUST DUCT.
Read the following carefully:
NOTE: It is important that venting be installed using
the most direct route and with as few elbows as possible.
This ensures clear venting of exhaust and helps prevent
blockages. $OVRPDNHVXUHGDPSHUVVZLQJIUHHO\DQG
QRWKLQJLVEORFNLQJWKHGXFWV
Exhaust connection:
The hood exhaust has been designed to mate with
a standard 3
1
ø4s x 10s rectangular duct.
If a round duct is required, a rectangular-to-round
transition adaptor must be used. Do not use less than
a 6s diameter duct.
0D[LPXPGXFWOHQJWK
For satisfactory air movement, the total duct length of
3
1
ø4s x 10s rectangular or 6s diameter round duct should
QRWH[FHHGHTXLYDOHQWIHHW
Elbows, transitions, wall and roof caps, etc.,
present additional resistance to airflow and are equivalent
to a section of straight duct which is longer than their actual
physical size. When calculating the total duct length, add the
equivalent lengths of all transitions and adaptors plus the
length of all straight duct sections. The chart below shows
you how to calculate total equivalent ductwork length using
the approximate feet of equivalent length of some typical
duct pieces.
Installation Instructions

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE JVM3160DFCC and is the answer not in the manual?

GE JVM3160DFCC Specifications

General IconGeneral
Styleover-the-range
Colorbisque
Total Capacity1.6 cu. ft.
Cooking Programsmicrowave
Control Optionspopcorn; beverage; potato; vegetable; reheat; defrost; weight/time
Convectionno
Power Levels10; yes
Fan Speeds2-speed
Venting Typeconvertible; externally vented
Sensor Cookingno
Quick Startyes; 1-6 minutes
Control Typeelectronic touch
Timeryes
Interior Lightincandescent - 2 bulbs; programmable night light; bright/night/off; incandescent; yes
Microwave Power1, 000 watts
Electrical Requirements120/60
Voltage120 volts
Current15
Weight and Dimensions IconWeight and Dimensions
Depth15 1/4 inch
Height16 1/2 inch
Width29 7/8 inch
Net Weight63 lbs.