EasyManuals Logo
Home>GE>Relays>Multilin 745

GE Multilin 745 User Manual

GE Multilin 745
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #157 background imageLoading...
Page #157 background image
S4 Elements
745
Transformer Management Relay
Setpoints
http://www.GEindustrial.com/multilin
5–83
GE Multilin
Current Demand PATH: SETPOINTS !" S4 ELEMENTS !" CURRENT DEMAND ! W1(3) CURRENT DEMAND
This section contains the settings to configure the current demand monitoring
elements. Included are a current demand level for each winding and each phase.
FIGURE 5–43: Current Demand Scheme Logic
! CURRENT DEMAND [!] W1 CURRENT DEMAND
FUNCTION: Disabled
Range: Enabled, Disabled
MESSAGE
W1 CURRENT DEMAND
TARGET: Self-Reset
Range: Self-Reset, Latched, None
MESSAGE
W1 CURRENT DEMAND
PICKUP: 100 A
Range: 0 to 65000 in steps of 1 (auto-
ranging)
MESSAGE
W1 CURRENT DEMAND
BLOCK: Disabled
Range: Logc Inpt 1 to 16, Virt Inpt 1 to
16, Output Rly 2 to 8, SelfTest
Rly, Vir Outpt 1 to 5, Disabled

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Multilin 745 and is the answer not in the manual?

GE Multilin 745 Specifications

General IconGeneral
BrandGE
ModelMultilin 745
CategoryRelays
LanguageEnglish

Related product manuals